Why yacht watermakers trip the inverter on starting
A watermaker is usually the largest step load on board. The high-pressure pump does not ramp up — it arrives all at once, and for a fraction of a second it draws several times the figure printed on the data plate. An inverter or breaker chosen against the running current will carry the unit perfectly well once it is turning and still trip every time it starts.
That is why the measurement is taken at the moment of starting rather than at rest. Voltage at the pump terminals as it cuts in, the length and condition of the run feeding it, and what the inverter or generator can actually deliver into a step load are what decide the fault — not the steady-state reading, which will usually look fine.
Scope of work
Supply sizing & electrical installation
Feed and high-pressure pump loads measured against what the bank, inverter or generator can deliver, then the supply, breaker and control wiring installed to suit the run length actually on the vessel.
Starting inrush current analysis
Inrush captured as the pump cuts in, to establish whether the inverter, the breaker or the cable run is the limit.
Control board & relay diagnostics
Start and stop logic, interlocks and relays traced circuit by circuit to find why a unit will not run, or will not stop.
Salinity sensor & diverter valve circuits
Conductivity probe, its wiring and the diversion valve circuit tested when product water is sent to waste continuously.
Fresh-water flush system wiring
Flush solenoid, its timer and their supply checked as one circuit — the one most often found dead after a winter layup.
Pressure & flow safety switches
Low-pressure and flow switches tested individually, including the dry-run protection that will stop a unit starting at all.

Attendance sequence
| Phase | Stage | Actions and deliverables |
|---|---|---|
| 01 | Symptoms by message | Vessel, berth, and whether it fails on starting, in service or on flush — plus whatever the control panel displays when it does. |
| 02 | Berth-side diagnostic | Voltage at the pump terminals measured as it cuts in, starting current captured, and the control, probe and flush circuits traced individually. |
| 03 | Written plan | Which circuit is at fault, what is repaired against what is replaced, and whether the limit is the supply or the unit itself. Where the fault is hydraulic, it is handed back as such. |
| 04 | Work, test, document | Circuits repaired, the unit run through a full cycle including flush, readings and photographs issued. |
Measurement and method
A watermaker fault is confirmed as electrical, or handed back as mechanical, on readings taken while the unit runs. Every measurement below is taken under power — a circuit that reads clean at rest tells you almost nothing about one that fails on starting.
Where this work is carried out
Delivered at the berth or in the yard across the North Adriatic.