Why the fault only appears on the pontoon
Marina trips, earth faults and voltage drop are measured under load with the shore lead connected. That is the only condition in which most of these faults appear — a circuit that reads clean at rest will still trip a pedestal the moment the vessel draws current.
Marina socket-outlets up to 63 A are individually protected by a residual current device rated at 30 mA or less, disconnecting all poles including neutral. Earth leakage that is harmless from any one appliance adds up across a whole vessel, so a boat that trips the pedestal is usually carrying several small faults rather than one large one.
Scope of work
230 V shore power & isolation
Shore inlet, isolation transformer and changeover arrangements, wired and tested with the lead connected.
RCD tripping diagnosis
Leakage measured circuit by circuit under load, to find which appliances contribute and by how much.
Galvanic isolation & corrosion
Galvanic isolator or isolation transformer specified and fitted, with the safety-earth path verified intact.
Earth-fault & voltage-drop tracing
Insulation resistance and voltage drop traced across the AC path from inlet to the furthest outlet.
Bilge pump & float switch circuits
Pump, float and alarm circuits tested — including a pump cycling with no water aboard, which is usually a float or wiring fault.
Panel rebuild & circuit labelling
AC panels rebuilt with correct protection and a documented circuit schedule replacing unlabelled legacy fusing.

Attendance sequence
| Phase | Stage | Actions and deliverables |
|---|---|---|
| 01 | Symptoms by message | Vessel, berth, which pedestal, and the trip pattern — on connection, under galley load, or intermittently overnight. |
| 02 | Berth-side diagnostic | Leakage measured circuit by circuit with the lead connected and the vessel under load, plus insulation resistance and voltage drop across the AC path. |
| 03 | Written plan | Which circuits contribute what leakage, what is repaired against what is replaced, and whether an isolator or a transformer suits the berth. |
| 04 | Work, test, document | Repairs made, protection verified, vessel reconnected and re-tested under load, readings and photographs issued. |
Measurement standards
Marina supply follows HD 60364-7-709 (marinas and similar locations) — transposed as HRN HD 60364-7-709 in Croatia, SIST HD 60364-7-709 in Slovenia and CEI 64-8/7 Sezione 709 in Italy.
Where this work is carried out
Delivered at the berth or in the yard across the North Adriatic. The marina wiring rules are harmonised across the three countries, with the national variations noted above.