How underwater lighting is assessed
An underwater fitting is cooled by the water it sits in. Operated in air, the LEDs reach their thermal limit within minutes and the protection circuit reduces output or shuts the fitting down. A fitting that dims on the hard and operates correctly afloat is therefore not necessarily faulty, and diagnosis is carried out with the vessel in the water — a test in air reproduces a condition that does not occur in service and masks the one that does.
Afloat, the two components that most often fail are the driver and the supply feeding it. Underwater fittings run through an external constant-current driver and are usually fed from a distribution point well forward of the transom, so volt drop across the run, corroded terminations and a driver operating below its input range account for most of what is reported as a failed light. Voltage is measured at the fitting with the circuit under load rather than at the panel, since that is where the difference appears.
Scope of work
Thru-hull & surface-mount installation
Fittings installed and sealed, wiring run and terminated, and the circuit commissioned. New hull apertures are cut with the vessel ashore and scheduled against the yard programme.
Constant-current driver replacement
Driver output measured against the fitting it feeds before it is condemned — a driver working below its input range behaves like a failed light and is not one.
Volt drop across extended runs
Measured at the fitting under load. Lighting circuits losing much more than three percent start showing colour shift and early driver failure rather than simply reading dim.
Bonding, isolation & galvanic protection
Whether a metal fitting is bonded to the vessel or deliberately isolated is decided per vessel and per hull material, then recorded — because getting it wrong in either direction creates corrosion rather than preventing it.
Switching, dimming & colour control
Switched and dimmed circuits, colour-change control and its wiring back to the panel or helm, including the control runs that fail while the lights themselves are fine.
Thermal cutout & fault diagnosis
Fittings that fade, cycle or cut out traced afloat under load, separating thermal protection operating correctly from a genuine electrical fault.

Attendance sequence
| Phase | Stage | Actions and deliverables |
|---|---|---|
| 01 | Symptoms by message | Vessel, berth, how many fittings are affected and whether the fault appears immediately or after a few minutes running — the timing separates a thermal response from a supply fault before anyone attends. |
| 02 | Berth-side diagnostic | Voltage measured at the fitting under load, driver output checked against its fitting, and bonding continuity or deliberate isolation confirmed against what the vessel is built as. |
| 03 | Written plan | Whether the fault is the fitting, its driver or the supply feeding it, what is repaired against replaced, and any hull work that has to wait for the vessel to come ashore. |
| 04 | Work, test, document | Circuits repaired or installed, then run afloat long enough to prove they hold output rather than cut back, with readings and photographs issued. |
What is measured
Underwater lighting is diagnosed afloat and under load. A fitting measured at rest, or in air, will read correctly and tell you nothing about the circuit that fails once it is drawing current and warming up.
Where this work is carried out
Diagnosis and driver, supply and control work at the berth across the North Adriatic. Hull apertures are scheduled with the vessel ashore.